A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HSiemens Desigo Dxr2
HWSiemenswszystkie wersjeSiemens Desigo Dxr2 Firmware
OSSiemens< 01.21.142.5-22Siemens Desigo Pxc3
HWSiemenswszystkie wersjeSiemens Desigo Pxc3 Firmware
OSSiemens< 01.21.142.4-18Siemens Desigo Pxc4
HWSiemenswszystkie wersjeSiemens Desigo Pxc4 Firmware
OSSiemens< 02.20.142.10-10884Siemens Desigo Pxc5
HWSiemenswszystkie wersjeSiemens Desigo Pxc5 Firmware
OSSiemens< 02.20.142.10-10884